Can you use a MG26547 Ground Fault Vigi Module by itself, without mounting it to a Multi-9 breaker?

No. This unit was designed to work with a two pole Multi-9 breaker of whatever amperage. The Vigi Modules are an accessory for the Multi-9 breakers and will not function on their own.