Can EZ Meter-Pak Main Lugs Tap Boxes (400A - 2000A) be installed as Service Equipment?

Issue:
Product Design Feature

Product Line:
EZ METER-PAK Multi-Metering Equipment

Environment:
EZM Main Lugs Tap Boxes

Cause:
Application

Resolution:
Yes, the following EZM Tap Boxes are suitable for use on the LINE side or LOAD side of Service Equipment.
They are shipped with isolated neutrals and each is supplied with a neutral bonding kit for use when required.
EZM1400TB, EZM1400TBU, EZM1600TB, EZM1800TB, EZM1800TBCU, EZM1800TBU, EZM11200TBU, EZM11600TB, EZM12000TB;
EZM3400TB, EZM3400TBU, EZM3600TB, EZM3800TB, EZM3800TBCU, EZM3800TBU, EZM31200TBU, EZM31600TB. EZM32000TB.

Note, that the 225A Tap Boxes (Cat. No.: EZM1225TB and EZM3225TB) are supplied with isolated neutrals that can not be bonded, and can not be used on the LINE side of Service Equipment.