Do 200 amp 35 kV loadbreak one piece bushings and loadbreak inserts have the same loadbreak elbow interface?

No. One piece bushings use an ANSI/IEEE Std. 386 Fig 8 interface. Inserts use an ANSI/IEEE Std. 386 Fig 7 interface. The elbows are not interchangeable.