What is the maximum total length of load wire that can be used with a QO-GFI or QO-EPD circuit breaker?

Product Line:
Ground Fault Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
The GFI breaker can be used with a 250 ft. maximum circuit length. We do not publish a maximum length for EPD breakers, but the maximum circuit length could be be considerably longer because of the higher GF pickup level.