What tenant circuit breakers are available for the 200 ampere maximum type MP, MPR, or MPH Meter-Pak Meter Centers?

Meter Pak Tenant breakers

Product Line:
Meter Pak metering

Tenant breakers


The 200 ampere maximum type MP, MPR and MPH Meter-Pak Meter Centers will accept type QOM2_ _MM(10k AIC) or QOM2_ _MVH(22k AIC) tenant circuit breakers, and are available in 100, 125, 150, 175 and 200 ampere sizes.

NOTE: Though they are the same QOM2 Type breakers as the Main Breakers(MB) used in QO and Homeline Load centers, they are NOT the same catalog numbers and are NOT interchangeable with the MB's in the load centers, NOR can the MB's from load centers be used in the Meter Pak devices.