Why does the FFTK screen occasionally display ?Failed? when performing short time test right after long time test in automatic mode for Micrologic A/P/H trip unit?<br />

This is normal due to the overlapping short time and long time curves. Wait at least 10 seconds after long time test before performing short time test.