What is the maximum amperage of branch breaker that can be used in the QO13040L200WG riser panel?

Product Design Features

Product Line:
QO load centers

Branch breakers


This riser panel has the interior shifted to the left (panel oriented with main lugs at top), which will restrict the branch breakers mounted on the left side to 30A Max. or less. Then the maximum branch breaker that can be used on the Right side of the interior (oriented with main lugs at top) is 125amp Max. 