Are there alternate lugs for the 600A HCP14506 interior, that will accept (3) - 4/0 conductors per phase?

Issue:
Are there alternate lugs for the 600A HCP14506 interior, that will accept (3) - 4/0 conductors per phase?

Product Line:
I Line panelboard

Environment:
Terminations

Cause:
Clarification

Resolution:
There are no alternate lugs for this wire size and amount per phase.. Recommend a HCP14508 800A interior instead