On a QOE250GFINM where do you connect the white neutral wire?

Issue:
Wiring

Product Line:
Enclosed Circuit Breaker

Cause:
Wiring assistance

Resolution:
The white "pigtail" neutral from the QO250GFI circuit breaker is factory connected to the device's neutral bar. The branch circuit neutral wire should be connected to the ``Load Neutral`` terminal on the QO250GFI.