Technical FAQs

Ask a Question

Does Square D offer a 30mm 9001K control station rated for use in hazardous locations?

Issue:
Does Square D offer a 30mm 9001K control station rated for use in hazardous locations?
Product Line:
30mm Push Buttons                       
Environment:
Type K and SK Electrical Components
Cause:
Determine is Schneider Electric has an control station to offer for this application.               
Resolution:                                                                 
Yes , but only for Class 1 Division 2 or Class II Division 2 Groups E & F.  Any Nema 4 & 13 enclosure ( ie. 9001KY** , KYSS** , SKY*** ) can be used,  if hermetically sealed contact blocks ( ie. 9001KA41 , 51 ) are used with 9001K or SK operators ( except potentiometers ) .
 
Was this helpful?
What can we do to improve the information ?