Is there an optional neutral lug or ground lug for a Homeline loadcenter that will accept a larger wire than the standard neutral bar or ground bar will accept?

Issue:
Selection

Product Line:
HOM Load Center

Cause:
Selection

Resolution:
Yes, there are optional, field installed neutral lugs that can be installed on most Homeline loadcenters. They could also be installed on an equipment ground bar. The options include: LK70AN (#12-2 Al or #14-4 Cu), LK100AN (#6-2/0 Al/Cu), LK125AN (#14-2/0 Al/Cu), LK150AN (#2-3/0 Al/CU) or LK225AN (#4-300 kcmil Al/CU).