What is the torque setting for the lugs contained in the DASK transformer lug kits on page 14-11 of Digest 176?

Torque for Transformer lugs 

Product Line:
LV Transformers

Applies to Lug Kits for Transformers by SquareD/Schneider Electric

Lugs require nuts and bolts properly torqued to attach them to the Transformer terminals

For the 1/4`` screws , the torque value is 6 lb/ft. For the 3/8`` screws the torque value is 19 lb/ft, referenced from UL486.  See attached document for more information about torque values for fastener hardware and set screws.