Can a QO or Homeline 2-pole EPD breaker be used to feed a 240V load that does not have a load neutral wire?

Issue:
Can a QO or Homeline 2-pole EPD breaker be used to feed a 240V load that does not have a load neutral wire?

Product Line:
QO-EPD, HOM-EPD

Environment:
Minature Circuit Breakers

Cause:
Application Assistance

Resolution:
Yes. Simply terminate the two hot wires on the breaker and leave the neutral lug unattached. The pigtail wire on the breaker should still be connected to the neutral bar in the panel - this is required to power the push to trip/test feature which verifies the status of the ground fault electronics.