What is the torque required to tighten the 1/4-20 mounting nuts to mount a QOM2-VH main breaker in a load center?

Product Line:
Circuit Breakers

Electrical Distribution Equipment

When the main breaker connector mounting nuts are loosed or removed, retighten to 75 Lbs./In. torque.