Technical FAQs

Ask a Question

Where can the breaker adapter kit part EZM125QOA be installed in the EZM metering?

Issue:
Product Features

Product Line:
EZM metering

Environment:
Accessory installation

Cause:
Application

Resolution:
EZM125QOA adapter kits are used to convert a bolt-on 2-Pole tenant circuit breaker position to a plug-on style tenant circuit breaker position in the following meter center branch units:

MPL units that make use of bolt-on, 2-Pole, 70A-225A,
Type QBP-TM, QDP-TM, QGP-TM or QJP-TM tenant circuit breakers can use this adapter with 2-Pole, 40A-125A, Type QO, QO-VH or QOH circuit breakers.

EZM, EZMR, EZMH or EZML branch units that make use of 2-Pole, 100A-200A,
Type Q2M, Q2M-VH, Q2MH circuit breakers can use this adapter with 2-Pole, 40A-100A, Type QO, QO-VH or QOH circuit breakers.

EZM, EZMR, EZMH, EZML or EZMT branch units that make use of 2-Pole, 100A-225A
Type, QDP-TM, QBP-TM, QGP-TM or QJP-TM circuit breakers can use this adapter with 2-Pole, 40A-125A, Type QO, QO-VH or QOH circuit breakers.

NOTE: The EZM125QOA adapter can not be used in MP, MPR or MPH units that make use of type QOM2-MM, or QOM2-MVH circuit breakers.
This adapter CANNOT be used in EZM, EZMR, EZMH, EZML or EZMT units that make use of type QE-VH circuit breakers.



CTA-ID : 2025683
Was this helpful?
What can we do to improve the information ?