Customer is missing the B phase light on a SDSA3650 connected to a 480v grounded B phase system.

Customer to check the wiring. Per the instuctions connect one black lead to A phase and the other 2 black leads to C phase. The white lead connects to the B phase. If one of the black leads is connected to B phase that LED will not light.