Can the QO, 3-phase FIXED Main Lug ONLY load centers be converted to a Main Breaker load center?

Product Features

Product Line:
QO 3phase load centers

Convertibility of mains


The QO, 3phase FIXED main lug ONLY load centers CANNOT be converted to a standard Main Breaker. 

NOTE: the only option would be to back feed a branch breaker on the interior, BUT the branch breaker is limited to 100amp MAX and a retaining bracket kit is required, part number PK3MB and the branch breaker will require 3 pole spaces on the interior.