Technical FAQs

Ask a Question

What is the voltage and current ratings of the Tesys U-Line built in auxiliary and auxiliary contact modules?<br />

Product Line:
 
Tesys K Line Contactors
 
Resolution:
 
The built in and add on auxiliary modules are rated B600 & P150 as outlined below:

B600 - AC Circuits
Maximum continuous carrying current = 5 amps
Maximum make current at 120 volts = 30 amps
Maximum break current at 120 volts = 3 amps
Maximum make current at 240 volts = 15 amps
Maximum break current at 240 volts = 1.50 amps
Maximum make current at 480 volts = 7.50 amps
Maximum break current at 480 volts = 750 milliamps
Maximum make current at 600 volts = 6 amps
Maximum break current at 600 volts = 600 milliamps
Maximum make volt-amps = 3600 VA
Maximum break volt-amps = 360 VA

P150 - DC Circuits
Maximum continuous carrying current = 5 amps
Maximum make or break current at 125 volts = 1.10 amps
Maximum make or break volt-amps at 300 volts or less = 138 VA


CTA-ID : 2023394
Was this helpful?
What can we do to improve the information ?