Will electronic ballasts on flourscent lamps cause a Home line GFI circuit breaker to open?

Electronic ballasts may generate harmonics which make a GFI QO or HOM breaker prone to nuisance tripping. Inrush currents and capacitive discharge to ground can also contribute. Limiting the number of ballasts on a circuit to five or fewer is recommended to avoid nuisance tripping.