Can the HQO****** distribution panel for I-Line panels accommodate a QO120GFI breaker ?

Issue:
Can the HQO****** distribution panel for I-Line panels accommodate a QO120GFI breaker ?

Product Line:
I Line panelboard

Environment:
Application 

Cause:
Clarification

Resolution:
Yes , 15-30a 1p or 2p QO GFIs will fit, but the HQO distribtuion load centers have (6) 1 pole space provisions , so for 1 pole GFI's only 3 maximum can be installed and (2) 2 pole GFI's maximum can be installed in the HQO panel.