Handle replacement HRPA does not fit on a PA breaker produced before 1975. Is there a replacement handle for this older breaker?

The breaker handle is not replaceable on the older PA breakers. The handle stub is connected to B phase, so DO NOT use visegrips or other tools on the handle stub. You must replace the breaker.