What can be done to solve nuisance tripping with a HOM breaker on a microwave circuit ?

Use a HOM115HM or HOM120HM for HOMELINE load centers or QO115HM or QO120HM for QO load centers. The HM suffix provides a breaker with a higher inrush withstand capability to allow the microwave to function .