Are the neutral assemblies used in General Duty Safety Switches isolated and insulated?

Product Design Features

Product Line:
General Duty Safety Switches

Solid Neutral Assembly


Yes. ALL the neutral assemblies used in the General Duty Safety Switches are Isolate and Insulated as standard. The switches that come with a neutral will contain a bonding strap or if the neutral is ordered separately, it will contain a bonding strap, so the neutral can be bonded for Service Entrance Applications. Once the neutral is bonded, it is NO longer isolated from the enclosure, but it does still remain insulated.