How far apart do you put hangers on an 800A horizontal busway section?

Indoor busway, mounted horizontally, must be supported at least every 10 feet. When it is mounted vertically, it must be supported at least every 16 feet. Outdoor busway must be supported at least every 5 feet regardless of the orientation..