Technical FAQs

Ask a Question

What is the maximum horsepower capacity for a 9013 FHG?

9013FHG2,9,12,13,44 and 49
single phase
115volts- 1.5HP
230 volts- 2HP

3- phase
115volts- 2HP
230 volts- 3HP
460/575 volts 1HP

DC
115volts- .25HP without FormM4
230 volts- .25HP ``

Control circuit rating
A600


9013FHG22 , 29 , 32, 53, 54, 59
single phase
115volts- 2HP
230 volts- 3HP

3- phase
115volts- 3hp
230 volts- 5hp
460/575 volts 1hp

DC
115volts- 1/2HP (.25hp with Form M1 )
230 volts- 1/2HP ``

Control circuit rating
A600




CTA-ID : 2024427
Was this helpful?