Can the operating time be reset to zero on the ATS48?

Yes.  Can go into the dRc menu and in the rPr code set the following.
- no: function inactive
- APH: kWh reset to zero
- trE: operating time reset to zero
The reset command must be confirmed with ENT. APH and trE take effect immediately.
The parameter then automatically returns to no.