Can there be a cable tap off the HVL switchgear main bus in a 22`` wide transition section.

Issue:
Can there be a cable tap off the HVL switchgear main bus in a 22`` wide transition section.

Product Line:
HVL Switchgear.

Environment:
Products sold in the United States.

Cause:
Application.

Resolution:
No. The tap off needs to be done with a line side connector assembly. This will not fit in a 22`` section. The tap off needs to be in a 38`` wide section.