Technical FAQs

Ask a Question

Is it ok to use an ATS48 with a Corner Grounded Delta, Ungrounded Delta, or Open Delta system?

It is ok to use Corner Grounded Delta with an ATS48.
However, some problems may occur on Ungrounded systems. One or more phases may have a high voltage with respect to ground and may cause measurement irregularities that can affect the operation of the soft starter.
The Open Delta may be a problem because the voltage may not be balanced when loaded. This may cause phase fault problems.

Reviewed 10/2011


CTA-ID : 2023862
Was this helpful?
What can we do to improve the information ?