Can 3-phase IN, 1-phase OUT EZM Branches be used in the same line up with 3-phase IN, 3-phase OUT EZM Branch devices? Do the single phase OUT device have to be used in certain positions?

Issue:
Installation of EZM branch devices

Product Line:
EZM Metering

Environment:
Three phase and single phase Branch devices

Cause:
Metering application requirements

Resolution:
The 3-Phase IN, 1-Phase OUT EZM Branch Devices Can be used with 3-Phase IN, 3-Phase OUT branch devices in the same line-up as long as the system is 3Phase Incoming.

These devices DO NOT have to be used in any certain positions within the line up. There are specific mounting requirements for the EZM Main Devices and possibly specific branch devices that must be used depending on the EZM Main Size(amp rating). See the EZM Mounting Instructions OR digest 176 page 2-8, lower left corner under the heading "Main Devices"