Will a QO2100 breaker fit into an NQOD20M100CU panelboard as a back fed main breaker?

It will physically fit but will violate the National Electric Code (NEC) for securing the breaker to the bus. Suggest use only the QOB2100 (bolt-on breaker) as the back fed main breaker.