What is the coil consumption or burden for the Tesys LC*D** contactors?<br /><br />* 1 or 2<br />** 09 through 38

Product Line:
 
Tesys D line Contactors
 
Resolution:
 
All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.