I am trying to replace a 10 foot section of AP510 busway. The busway is obsolete, so what can I use?

You can replace that old busway 10 foot section with an 8 foot section of new plug-in busway and two of the one foot adapters. Catalog numbers are: AF2510G12S for the slot adapter, and AF2510G12B is the bolt adapter. AP2510G8ST is the plug-in straight piece that goes between them. It is advisable to get an AT2 assembly tool and HF53F hangers, as well.