Can a three phase isolation transformer with the standard delta primary be applied on a wye configuration power system?

Issue:
Transformer power is often provided by a Wye service
 
Product Line:
LV Transformers
 
Environment:
Applies to Three Phase SquareD/Schneider Electric Transformers
 
Cause:
Most Three Phase Transformers by SquareD/Schneider Electric have Delta Primaries
 
Resolution:
Yes, a three-phase, delta primary isolation transformer can be used on any three-phase system. Just like a motor, the transformer only needs to have a balanced three-phase voltage applied to its` terminals.