What are the torque specifications for the lugs on a PBTB506G plug in tap box?

Issue:
What are the torque specifications for the lugs on a PBTB506G plug in tap box?

Product Line:
I-Line Busway and Accessories

Environment:
Installation

Cause:
Maintenance

Resolution:
The wire binding screws on the lugs should be torqued to 375 lb-ins, or about 31 lb-ft. See the instruction label on the inside of the device.


 