What is the significance of the LA6DK10 footnote ``Does not include internal coil clearing contact.``?

Most mechanically held contactors are provided with a coil clearing contact so the coil does not remain energized, otherwise it would hum. Also in this device the coil is not rated for continuous duty. Keeping the latch block coil energized will burn up the coil. A normally closed auxiliary contact can be wired in series with the coil to achieve this.