Technical FAQs

Ask a Question

Can a EZM Meter Branch Device be mounted to either the right or left side of a EZM Main Device?

Issue:
EZM metering line up Assembly 

Product Line:
EZM Metering

Environment:
Installation

Cause:
Meter Branch Device mounting

Resolution:
Yes, in some cases the EZM branch devices can be mounted on either the left or right side of a Main Device. BUT there are some mounting restrictions depending on the Main device ampere rating and the catalog number of the EZM main. REFER to the EZM instructions that come with all the EZM main devices. Also, see note below.

NOTE:  The Main Devices rated through 800 ampere may have Branch Devices mounted to either side. Main Devices rated 1,000 or 1,200 ampere must be center mounted when used with Branch Devices with 800 ampere cross bus. Main Devices rated 1,000 or 1,200 ampere may have Branch Devices with 1,200 ampere cross bus mounted to either side. Main Devices rated 1,600 ampere must be center mounted in all cases. Main Devices rated 2000 ampere must be center mounted in ALL cases and requires the use of branch devices having 1200amp horizontal cross bus. 


CTA-ID : 2021852
Was this helpful?
What can we do to improve the information ?