Technical FAQs

Ask a Question

What is the lug size for the ATS48D62Y, ATS48D75Y, ATS48D88Y or ATS48C11Y

The ground conductor is max of 4 AWG and Power Terminals are max of 2/0 AWG.
It is not necessary to provide lugs for this soft starter. The terminals are part of the unit.


CTA-ID : 2020663
Was this helpful?
What can we do to improve the information ?