What is the lug size for the ATS48D62Y, ATS48D75Y, ATS48D88Y or ATS48C11Y

The ground conductor is max of 4 AWG and Power Terminals are max of 2/0 AWG.
It is not necessary to provide lugs for this soft starter. The terminals are part of the unit.