Can the secondary main breaker in an MPZ10S40F be a GFI breaker?

The standard secondary main breaker is a QO260. If a QO260GFI were used, the secondary would no longer have a neutral connection and would be limited to 240 volts only and no single-pole 120V branch breakers would be allowed.