Technical FAQs

Ask a Question

What effect does the installation of weathershields have on the minimum distance between a vertical (wall) surface and the Transformer ?

Issue:
Clearances of Transformers

Product Line:
LV Transformers

Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric

Cause:
Transformer heat dissipation requires clearance from obstructions

Resolution:

The minimum clearance applies only to a Transformer without weathershields. Once that distance is established, you may add the weathershields without violating the clearance requirement.


CTA-ID : 2020958