What is the part number for a varistor coil surge suppressor for a LC1D09 to LC1D32 3 pole and LC1DT20 to LC1DT40 4 pole?

Surge suppressor part number is needed

Product Line:
NEMA combination starters

Products sold and used in the United States

Need a varistor coil surge suppressor in their application

For 24 to 48 volts LAD4VE, for 50 to 127 volts LAD4VG, and for 110 to 250 volts LAD4VU.
These will limit the transient to 2 times nominal voltage and increases drop out time 1.1 to 1.5 times normal.