Technical FAQs

Ask a Question

When using a EZM Main Breaker or Fusible Switch(single or three phase) as the Utility Main, can a EZM Main Terminal(or Tap) box be used as a branch feeder?

Issue:
Current design features

Product Line:
EZM Metering

Environment:
EZM Mains

Cause:
Application

Resolution:
Yes, it is permissible to use a EZM main terminal(or tap) box as a branch feeder to a down stream load, if the main bussing of the Utility main device is the same amperage or higher, as the terminal(or tap) box being applied as the branch feeder.


CTA-ID : 2021138
Was this helpful?
What can we do to improve the information ?