When using a EZM Main Breaker or Fusible Switch(single or three phase) as the Utility Main, can a EZM Main Terminal(or Tap) box be used as a branch feeder?

Current design features

Product Line:
EZM Metering

EZM Mains


Yes, it is permissible to use a EZM main terminal(or tap) box as a branch feeder to a down stream load, if the main bussing of the Utility main device is the same amperage or higher, as the terminal(or tap) box being applied as the branch feeder.