What is the DB brake part number or size for an ATS48 soft starter?

Soft starters can not perform dynamic braking.
There is a function called Intelebraking. It is designed to provide a small amount of braking torque for a motor.

When using INTELE braking, the stop time is less than the freewheel
stopping time. INTELE braking is a two-part braking process which does
not require external components. It produces less motor heat than traditional
DC injection braking.
INTELE braking is best used when all of the criteria below are met:
? 4-pole or 6-pole motors only
? motor slip is less than or equal to 3%