Can the Powerpact Q Frame Circuit Breaker be 100% rated?

Issue:
Can the Powerpact Q Frame Circuit Breaker be 100% rated?

Product Line:
Powerpact Q Frame

Environment:
Circuit breaker application requiring a 100% rating or fully rated breaker.

Resolution:
NO - These QB, QD, QG, nad QJ breakers are standard, or 80% rated, only .

For 100% rated application look to the Powerpact H and J Frames, and for ILINE applications look to the Powerpact L Frame.