Technical FAQs

Ask a Question

Are alternate lugs available for the EZM3800FS?

Issue:
Product Design Features

Product Line:
EZ Meter-Pak Metering Equipment - EZM

Environment:
Alternate Main lugs 

Cause:
Non-standard or larger wire sizes

Resolution:
Yes, the standard mechanical lugs will accommodate (3) 500 Kcmil AL/Cu wires maximum per phase and neutral.
For alternate lugs see below:
1) For (2) 600 Kcmil Al/Cu Maximum per phase and neutral use the AL800MA7 lug kit for the molded case switch and the MMLK250 lug kit for the neutral.

2) For (2) 750 Kcmil Al/Cu Maximum per phase and neutral use the AL800MA7 lug kit for the molded case switch and the MMSK2 Lug landing kit with (2) ILSCO Lugs, TA8002N(Purchased separately) for the neutral.
NOTE: For the MMSK2 Kit, this kit includes three lug landing pads, use only the two lug landing pads having the smallest offsets. Do not use the connector with the large offset. Attach the ILSCO lugs to the Lug landing pads and then to the neutral.

3) For (4) 350 Kcmil Al/Cu Maximum per phase and neutral use (3) AL1000MA for the molded case switch and the standard neutral Lugs that come on the device.


CTA-ID : 2019238
Was this helpful?
What can we do to improve the information ?