Technical FAQs

Ask a Question

What terminals do I use to land the zone interlocking wires on a LE36400LIG breaker?

Terminals 5 & 6 are for short time restraint, 7 & 8 are for ground fault, and terminal 9 is common.


CTA-ID : 2019298
Was this helpful?
What can we do to improve the information ?