Is the QOB3150VH the largest breaker that can be mounted in an existing NQOD panel?

Issue:
Is the QOB3150VH the largest breaker that can be mounted in an existing NQ or NQOD panel?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
Yes because the QOB3150VH mounts in a branch location, requires 6 vertical pole spaces and only 20A max breakers can be mounted across from it due to the rating of the branch connector. Larger breakers must be installed as sub-feed breakers and are available in NQOD panels as factory assembled only.

Revised 6/25/04