What is the Short Circuit Current Rating of General Duty switches?

The SCCR for General Duty switches is dependent upon the type of fuses used in or protecting the switch. Using Class H or K fuses, SCCR is 10,000 AIC. Using Class R, J, T or L fuses, SCCR is 100,000 AIC.