Technical FAQs

Ask a Question

What is the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38

Issue:
What is the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38

Product Line:
D Line contactor.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
AC single frequency coils: 50Hz and 60 Hz (-20% / +10%);
AC dual frequency coils: 50Hz (-20% / +10%) ; 60Hz (-15% / +10%)
DC standard coil for LC1D09 -D38 and LC1DT20 to DT40: (-30% / +25%)
DC standard coil for LP1D12 and D25: (-20% / +10%)
DC wide range coil for LP1D12 and D25 : (-30% to +25%)


CTA-ID : 2018707
Was this helpful?
What can we do to improve the information ?