What is the operating temperature rating on the ATS48?

14 to +104 *F (-10 *C to +40 *C) without derating.

Up to +140 *F (+60 *C), derate the current by 2% for each *C above 40 *C.

14 to 122 *F (-10 *C to +50 *C) with user provided shorting/bypass contactor.