Technical FAQs

Ask a Question

Can electronic dimmers be used on Buck/Boost Transformers ?

Buck Boost Transformers are often used to power incandescent lights which must be dimmed

Product Line:
LV Transformers

Applies to Buck Boost Transformers by SquareD/Schneider Electric

The transformer winding presents a different type of load profile to the dimmer than an incandescent light does


Dimmers can be used to control Buck and Boost Transformers only if the dimmer circuit is of high enough quality to reproduce an AC sine wave properly at the output.  Also, electronic dimmers that develop any DC voltages at their output can cause the Transformer windings to overheat and burn out, which is a distinct possibility with some types of inexpensive dimmers

CTA-ID : 2017810

Was this helpful?
What can we do to improve the information ?